Yibin 5GW High Crystalline Silicon Battery Project Energy Saving Report Approved!

2023-11-28 17:22:44

The annual power consumption is 27547, 1,000 kilowatt-hours, and the annual comprehensive energy consumption is equivalent to the standard coal equivalent 34224, 34 tons..

Yibin Yingfa Deyao Technology Co., Ltd.:

We have received your Request for Submission of Energy-saving Report on the Construction Project of Intelligent Production Line of 5G W High-efficiency Crystalline Silicon Solar Cells with Annual Output, and we have entrusted Sichuan Engineering Consulting Institute to review the energy-saving report of the project. The review organization issued the Report on the Review Opinions on the Energy-saving Report of the Construction Project of the Intelligent Production Line of 5G W High-efficiency Crystalline Silicon Solar Cells with Annual Output (CGZG [2023] No.766). After review, the review opinions are as follows:

I. The energy conservation report of the project (project code: 2208-511504 -04-01-739473) is approved in principle.

2. Type and quantity of annual energy consumption of the project: The annual power consumption when the project is put into normal operation is 10,000 kilowatt-hours of 27547 and 303,800 cubic meters of natural gas; 2.453 million cubic meters of fresh water purchased, 0.24 million cubic meters of self-produced compressed air 10065, 13.613 million cubic meters of nitrogen and 157.7 million cubic meters of oxygen (energy-consuming working medium, not included in energy consumption). The annual comprehensive energy consumption is equivalent to 0.34 tons of standard coal equivalent 34224 and 0.44 tons of equivalent 90723 (the electricity equivalent value and the equivalent value are calculated at 0.1229 and 0.328 kg of standard coal/kWh respectively).

3. Energy efficiency level. The comprehensive power consumption and water consumption per unit product of the crystalline silicon battery (P-type) of the project are 54,600 kW ∙ H/MWp and 490.6t/MWp respectively. All of them meet the requirements of comprehensive power consumption per unit product of crystalline silicon cell < 80,000 kW ∙ H/MWp and water consumption per unit product of crystalline silicon cell < 750 t/MWp in the Standard Conditions for Photovoltaic Manufacturing Industry (2021 edition). The energy consumption (equivalent value) of unit output value and unit industrial added value of

the project is 0.244 TCE/10,000 yuan and 1.319 TCE/10,000 yuan respectively.

4. On the basis of implementing various measures of the energy conservation report, the project design and construction units shall, The following energy-saving work shall be improved and strengthened:

(1) In view of the fact that the energy consumption of the main equipment such as diffusion machine, coating machine, annealing machine, oxidation machine, drying furnace, sintering furnace, texturing machine, water heater, electric injection machine, tank alkaline polishing and cleaning equipment, sorting machine, oven, fan, air compressor and water pump accounts for a large proportion of the total energy consumption, the construction unit shall purchase the equipment in the next stage. According to the production scale and process requirements, strictly implement the principle of project equipment selection, use energy-consuming equipment that meets the requirements of energy-saving level, and give priority to the energy-saving technology, production process and energy-consuming equipment in the National Key Energy-saving and Low-carbon Technology Promotion Catalogue and other relevant catalogues.

(2) In accordance with the General Principles for the Allocation and Management of Energy Measuring Instruments in Energy-using Units (GB17167-2006), the allocation design of energy measuring instruments shall be refined and implemented, and a sound energy measurement management system shall be established; In accordance with the Measures for Energy Conservation Management of Key Energy-using Units (Decree No.15, 2018) issued by the National Development and Reform Commission and other seven departments, an online energy consumption monitoring system will be built to connect the energy consumption monitoring data to the provincial platform of the online energy consumption monitoring system of key energy-using units in Sichuan Province.

5. When the energy consumption process and equipment, energy consumption variety, construction content and scale of the project have changed significantly or the actual annual comprehensive energy consumption exceeds the level specified in this review opinion by more than 10%, the project construction unit shall conduct a new energy conservation assessment and report it to the Commission for review. If the authority of the project energy conservation review changes, it shall be submitted to the competent review authority for handling in a timely manner.

6. According to the Implementation Measures for Energy Conservation Review of Fixed Assets Investment Projects in Sichuan Province, the project construction unit is requested to carry out the energy conservation review and acceptance of the project and prepare the energy conservation review and acceptance report before it is formally put into production and use. Those who pass the examination and acceptance of energy conservation shall submit the acceptance report to the Provincial Development and Reform Commission for filing. Projects that have not been accepted or failed to pass the acceptance shall not be put into production and use.

7. The Yibin Municipal Development and Reform Commission is requested to effectively supervise and inspect the design, construction, completion acceptance and operation management of the project in accordance with the review opinions and the energy-saving report of the project, and timely report on the implementation of the review opinions and major matters related to the project. We should further optimize the allocation of energy factors, fully tap the potential of energy conservation, promote the improvement of energy efficiency, strengthen the target management of energy intensity reduction, and ensure the completion of the "14th Five-Year Plan" energy-saving target task issued by the provincial government.

8. The Provincial Energy Conservation Regulatory Affairs Center is requested to carry out energy conservation supervision on the implementation of the project energy conservation review opinions in accordance with the Measures for Energy Conservation Supervision (Decree No.33 of 2016 of the National Development and Reform Commission).

9. This opinion only provides review opinions on the project energy conservation report, and the project construction management shall be strictly implemented in accordance with relevant laws, regulations and policies.

10. This review opinion shall be valid for 2 years from the date of issuance. Projects that fail to start construction within the time limit or whose completion time exceeds the expected completion time in the energy-saving report for more than two years shall be re-examined for energy conservation.

Attachment: Basic Overview of the Construction Project of Intelligent Production Line with Annual Output of 5G W High-efficiency Crystalline Silicon Solar Cells

Sichuan Development and Reform Commission

November 20

, 2023 Attachment

: The second phase of Sichuan Yibin Yingfa Deyao High-efficiency Crystalline Silicon Solar Cell Production Project was launched, and the third and fourth phases of the project were launched. It is understood that Yingfa Deyao Company has signed four projects with Yibin High-tech Zone in Sichuan Province, with a total investment of 21.5 billion yuan, and the annual output value will exceed 50 billion yuan after full completion and full production. According to

the data, Yibin Yingfa Deyao is the third largest battery production base of Yingfa Group. It is expected that by the end of this year, Yingfa's battery production capacity will reach 30GW. Yingfa Group has made every effort to build Yibin Yingfa 50GW high-efficiency crystalline silicon solar cell production base.

All can be viewed after purchase
Correlation

The annual power consumption is 27547, 1,000 kilowatt-hours, and the annual comprehensive energy consumption is equivalent to the standard coal equivalent 34224, 34 tons..

2023-11-28 17:22:44